Content (measure theory)

From formulasearchengine
Revision as of 20:26, 8 December 2013 by en>R.e.b. (→‎Integration of bounded functions: Expanding article)
Jump to navigation Jump to search
File:Fluke Networks 10G kit.jpg
10 Gb Certification Kit

In copper twisted pair wire networks, copper cable certification is achieved through a thorough series of tests in accordance with Telecommunications Industry Association (TIA) or International Organization for Standardization (ISO) standards. These tests are done using a certification-testing tool, which provide “Pass” or “Fail” information. While certification can be performed by the owner of the network, certification is primarily done by datacom contractors. It is this certification that allows the contractors to warranty their work.

Need for certification

Installers who need to prove to the network owner that the installation has been done correctly and meets TIA or ISO standards need to certify their work. Network owners who want to guarantee that the infrastructure is capable of handling a certain application (e.g. Voice over Internet) will use a tester to certify the network infrastructure. In some cases, these testers are used to pinpoint specific problems. Certification tests are vital if there is a discrepancy between the installer and network owner after an installation has been performed.

The Standards

The performance tests and their procedures have been defined in the ANSI/TIA/EIA-568-B.1 standard and the ISO/IEC 11801 standard. The TIA standard defines performance in categories (Cat 3, Cat 5e, Cat 6, Cat 6A) and the ISO defines classes (Class C, D, E, EA, F and FA). These standards define the procedure to certify that an installation meets performance criteria in a given category or class.

The significance of each category or class is the limit values of which the Pass/Fail and frequency ranges are measured: Cat 3 and Class C (no longer used) test and define communication with 16 MHz bandwidth, Cat 5e and Class D with 100 MHz bandwidth, Cat 6 and Class E up to 250 MHz, Cat6A and Class EA up to 500 MHz, Cat7 and Class F up to 600 MHZ and Cat 7A and Class FA with a frequency range through 1000 MHz.

The standards also define that data from each test result must be collected and stored in either print or electronic format for future inspection.

The Tests

Test Parameter TIA-568-B ISO 11801:2002
Wiremap Pass/Fail Pass/Fail
Propagation Delay Pass/Fail Pass/Fail
Delay Skew Pass/Fail Pass/Fail
Cable Length Pass/Fail Information only
Insertion Loss (IL) Pass/Fail Pass/Fail
Return Loss (RL) Pass/Fail (except Cat3) Pass/Fail
Near-End Crosstalk (NEXT) Pass/Fail Pass/Fail
Power Sum NEXT (PSNEXT) Pass/Fail Pass/Fail
Equal-Level Far-End Crosstalk (ELFEXT) Pass/Fail Pass/Fail
Power Sum ELFEXT (PSELFEXT) Pass/Fail Pass/Fail
Attenuation-to-Crosstalk Ratio (ACR) Information only Pass/Fail (except Class C)
Power sum ACR (PSACR) Information only Pass/Fail (except Class C)
DC Loop Resistance Pass/Fail

Wiremap

The Wiremap test is used to identify physical errors of the installation; proper pin termination at each end, shorts between any two or more wires, continuity to the remote end, split pairs, crossed pairs, reversed pairs, and any other mis-wiring.

See TIA/EIA-568-B for wiring diagram.

Propagation Delay

The Propagation Delay test tests for the time it takes for the signal to be sent from one end and received by the other end.

File:Propagation delay.gif

Delay Skew

The Delay Skew test tests for the difference in propagation delay between the fastest and slowest set of wire pairs. An ideal skew is between 25 and 50 nanoseconds over a 100 meter cable. The lower this skew the better; less than 25 ns is excellent, but 45 to 50 ns is marginal.

File:Delay skew.gif

Cable Length

The Cable Length test verifies that the copper cable from the transmitter to receiver does not exceed the maximum recommended distance of 100 meters in a 10BASE-T/100BASE-TX/1000BASE-T network.

Insertion Loss

Insertion loss, also referred to as attenuation, refers to the loss of signal strength at the far end of a line compared to the signal that was introduced into the line. This loss is due to the electrical impedance of the copper cable, the loss of energy through the cable insulation and the impedance caused by the connectors. Insertion loss is usually expressed in decibels dB with a minus sign. Insertion loss increases with distance and frequency. For every 3dB of loss, the original signal will be half the original power ( of amplitude).

Decibels vs. Voltage

dB Voltage Ratio dB Voltage Ratio dB Voltage Ratio dB Voltage Ratio
0 1V -6 .500 -13 .224 -19 .112
-1 .891 -7 .447 -14 .200 -20 .100
-2 .794 -8 .398 -15 .178 -30 .032
-3 .707 -9 .355 -16 .158 -40 .010
-4 .631 -10 .316 -17 .141 -50 .003
-5 .562 -11 .282 -18 .125 -60 .001
-12 .250 -80 .0001

Return Loss

Return Loss is the measurement (in dB) of the amount of signal that is reflected back toward the transmitter. The reflection of the signal is caused by the variations of impedance in the connectors and cable and is usually attributed to a poorly terminated wire. The greater the variation in impedance, the greater the return loss reading. If 3 pairs of wire pass by a substantial amount, but the 4 pair barely passes, it usually is an indication of a bad crimp or bad connection at the RJ45 plug. Return loss is usually not significant in the loss of a signal, but rather signal jitter.

Near-End Crosstalk (NEXT)

Near-End Crosstalk (NEXT) is an error condition that describes the occurrence of a signal from one wire pair radiating to and interfering with the signal of another wire pair. It is the difference in amplitude (in dB) between a transmitted signal and the crosstalk received on other cable pairs at the same end of the cabling. Higher NEXT values correspond to better cabling performance. A higher value is desirable as it would indicate that the power transmitted is greater in magnitude than the power induced onto another wire pair given that the NEXT measurement is simply a difference calculation. NEXT must be measured from each pair to each other pair in twisted pair cabling and from each end of the connection. NEXT is measured 30 meters (about 98 feet) from the injector / generator. Lower near end crosstalk values correspond to higher overall circuit performance. High NEXT values on a UTP LAN that will be using an older signaling standard (IEEE 802.3i and earlier) are particularly detrimental. It could be an indication of improper termination.


Power Sum NEXT (PSNEXT)

Power Sum NEXT (PSNEXT) is the sum of NEXT values from 3 wire pairs as they affect the other wire pair. The combined effect of NEXT can be very detrimental to the signal.

The Equal-Level Far-End Crosstalk (ELFEXT)

The Equal-Level Far-End Crosstalk (ELFEXT) test measures Far-End Crosstalk (FEXT). FEXT is very similar to NEXT, but happens at the receiver side of the connection. Due to attenuation on the line, the signal causing the crosstalk diminishes as it gets further away from the transmitter. Because of this, FEXT is usually less detrimental to a signal than NEXT, but still important nonetheless.

Power Sum ELFEXT (PSELFEXT)

Power Sum ELFEXT (PSELFEXT) is the sum of FEXT values from 3 wire pairs as they affect the other wire pair, minus the insertion loss of the channel.

Attenuation-to-Crosstalk ratio (ACR)

Attenuation-to-Crosstalk ratio (ACR) is the difference between the signal attenuation produced NEXT and is measured in decibels (dB). The ACR indicates how much stronger the attenuated signal is than the crosstalk at the destination (receiving) end of a communications circuit. The ACR figure must be at least several decibels for proper performance. If the ACR is not large enough, errors will be frequent. In many cases, even a small improvement in ACR can cause a dramatic reduction in the bit error rate. Sometimes it may be necessary to switch from un-shielded twisted pair (UTP) cable to shielded twisted pair (STP) in order to increase the ACR.

Power Sum ACR (PSACR)

Power Sum ACR (PSACR) done in the same way as ACR, but using the PSNEXT value in the calculation rather than NEXT.

DC Loop Resistance

DC Loop Resistance measures the total resistance through one wire pair looped at one end of the connection. This will increase with the length of the cable. DC resistance usually has less effect on a signal than insertion loss, but plays a major role if power over Ethernet is required. Also measured in ohms is the characteristic impedance of the cable, which is independent of the cable length.

Notes

  • International standard ISO/IEC 11801: Information technology — Generic cabling for customer premises
  • Telecommunications Industry Association (TIA) Commercial Building Telecommunications Cabling Standard - Part 1: General Requirements (ANSI/TIA/EIA-568-B.1-2001)
  • Telecommunications Industry Association (TIA) Commercial Building Telecommunications Cabling Standard - Part 2: Balanced Twisted Pair Components - Addendum 1 - Transmission Performance Specifications for 4-Pair 100 Ohm Category 6 Cabling (ANSI/TIA/EIA-568-B.2-1-2002)

See also